| Index >> Products >> Monitoring >> Sensors & accessories
Temp-232
A simple digital thermal sensor, communicating over RS-232 interface by a simple text protocol. Does not require power supply, the sensor is powered from PC's serial port.
Note: Product was canceled.
The
measured temperature is sent directly in °C by a simple text protocol.
The sensor sends the measured value regularly (in predefined interval) or as a respond to a request
according to a specific Question-Answer protocol.
The thermal sensor uses an integrated element with
accuracy of ± 0,5°C for temperature measuring. LED indicates that temperature measuring is in progress.
.
Application
- Temperature measuring systems
- Industrial measuring and regulation
- Temperature measuring in warehouses, production and residential premises
- After connection to Poseidon - measuring in technological premises and transferring data via Ethernet
Basic properties
- The sensor is connected to PC over standard RS-232
- Temperature measuring in range from -55°C to +125°C
- The sensor address and a period of automatic temperature reporting can be set in terminal SETUP mode
- It can operate in Question-Answer mode
- LED indication of measuring
- Simple communication protocol
- Does not require power supply, powered directly from PC serial port
- The sensor cooperates with SNMP thermometer Poseidon
Downloads & Datasheets
Technical specifications
| Basic parameters |
+ Range of measured temperature |
-55°C to +125°C |
| + Resolution format |
0,1 °C |
| + Measurement accuracy |
+/- 0,5 °C in range from -10°C to +85°C
+/- 2 °C in range from -55°C to +125°C |
| Communication |
| + Measuring speed |
Respond to query within 50ms at maximum, measuring itself 1x within a second |
| + Measuring element |
DS18B20 |
| + Data format |
ASCII, described in specification |
| + Communication parameters |
9600 8N1 |
| + Connector |
DB9F - Female (connected to PC directly) |
| + Communication line |
RS-232 (RxD, TxD, GND, DTR, RTS) |
| + Status indication |
Red indicator blinks at every measuring, ligths constantly in Terminal Setup mode |
| + Function modes |
Auto-Report / Question-Answer |
| - Auto-Report mode |
Temperature reported automatically in defined time,
period 1 .. 255 [seconds] |
| - Question-Answer |
Temperature reported on request according to protocol (request by a "t" character) |
| + Temperature format |
„+028.0C<CR><LF>“ |
| + Access to SETUP mode |
Sends „u“ (117 DEC) character 20x after turning on |
| + Turning on thermometer |
Setting DTR or RTS to „On“ value |

Sensor installation:
- Connect Temp-232 to PC port
- Run terminal program, choose serial port where the Temp-232 is connected, set speed to
9600, port parameters 8N1,
RTS and DTR output to „ON“
- In the terminal a temperature value will start to appear (in 2 second interval, preset in factory)
SETUP Terminal mode
- Turn on the thermometer (Set DTR or RTS to „On“ =
+12V)
- Access the SETUP mode by sending cca 20 „u“ (117 DEC) characters after turning on.
You can just hold the "u" key until the LED of the thermometer lights up.
- Choose parameters in Setup mode using the first letters of the desired command
|
DB9F on the cable  |
| 1 |
- |
- |
Not used |
| 2 |
TxD |
<-- |
Transmit Data |
| 3 |
RxD |
--> |
Receive Data |
| 4 |
PWR |
--> |
PWR input (from the DTR output) |
| 5 |
GND |
--- |
System Ground |
| 6 |
- |
- |
Not used |
| 7 |
PWR |
--- |
PWR input (from the RTS output) |
| 8 |
- |
- |
Not used |
| 9 |
- |
- |
Not used |
|
Ordering
The price can be found
on the Pricelist page.
| OID |
Detailed description |
| 600 051 |
Temp-232 1.5m
Temperature sensor encased in black covering (preferred
type), cannon DB9M, sensor on 1.5 m cable.
Product is not available any more. |
Similar products
- Damocles family
- Eth. I/O Controller
Connection of binary inputs and outputs over Ethernet along with a serial line.
Binary states can be just remotely monitored (I/O Controller in the Server mode),
or the device itself notifies of a change on the input pins (Client/Server mode).
|